The model
In a vapour-compression cycle, the evaporator absorbs heat from the cooled space, the compressor raises refrigerant pressure, the condenser rejects heat to the surroundings and the expansion device reduces pressure. The refrigerant does not remain in the same physical state throughout the cycle.
Refrigeration COP is the cooling capacity divided by the input power. The measurement boundary matters: does power include only the compressor, or also fans and pumps? COP figures stated at different operating conditions should not be compared directly.
Worked example
A system providing 20 kW of cooling with 5 kW of electrical input has a COP of 4 and rejects 25 kW at the condenser.
Scope & assumptions
Ammonia and fluorinated refrigerants can be examined using the same ideal-cycle concept, but their materials, oil, safety provisions and operating pressures differ. This reference and its companion calculator explain an energy balance; they do not supply a refrigerant-property library or select equipment.
TRY IT YOURSELF
Check your understanding.
Compare the COP with a system delivering the same cooling capacity while drawing 6 kW.
Sign-in required. Calculator interface currently in Turkish.
