Technical reference

Heat Transfer & Insulation

Separate heat flow through a surface from the total refrigeration load.

The model

A temperature difference drives energy transfer from the warmer side to the colder side. The conduction resistance of a flat layer is d/k. The overall U-value of a real wall combines its layers and surface resistances.

A steady surface calculation uses Q̇ = UAΔT. Use area in m², U-value in W/(m²·K) and temperature difference in K. A difference of 1 °C is the same interval as 1 K; this equivalence does not apply to absolute-temperature calculations.

Q̇ = U A (T_out − T_in)

Worked example

200 m² × 0.22 W/(m²·K) × 35 K gives a transmission heat flow of 1540 W.

Scope & assumptions

The total load of a cold room also includes product cooling, door air exchange, respiration, lighting, fans and defrost. The surface calculator estimates only the transmission contribution. Select a U-value from verified technical data for the construction.

TRY IT YOURSELF

Check your understanding.

Keep the area and temperature difference fixed, halve the U-value and interpret the change in heat flow.

Open the companion calculator ↗